Daikin RXYQ10PY1 [451/487] Control 843

Daikin RXYQ10PY1 [451/487] Control 843
ED34-645B Adaptor
Control 843
16
Fig. 2 (Ex.) To set the outdoor unit’s cool/heat address to No. 15 :
—Off —On —Flicker 5-bit
Procedure Setting contents MODE TEST
C/H SELECT
L.N.O.P.
SEQ.
START
IND MASTER SLAVE
When power turned on Setting mode (factory set)
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Hold down next page button for 5 sec. Enters address setting.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Push operation button one time. Enters cool/heat address setting.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Push confirmation button one time.
Make sure cool/heat address has been
entered. LED20 LED21 LED22 LED23 LED24 LED25 LED25
Push operation button 15 times.
(Address No. = Times pushed)
Sets cool/heat address.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Push confirmation button two times. Check cool/heat address.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Push next page button one time. Returns to set mode.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Fig. 3 (Ex.) To set the outdoor unit’s demand address to No. 7 :
—Off —On —Flicker 5-bit
Procedure Setting contents MODE TEST
C/H SELECT
L.N.O.P.
SEQ.
START
IND MASTER SLAVE
When power turned on Setting mode (factory set)
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Hold down next page button for 5 sec. Enters address setting.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Push operation button two times. Enters demand address setting.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Push confirmation button one time.
Make sure demand address has been
entered. LED20 LED21 LED22 LED23 LED24 LED25 LED25
Push operation button 7 times.
(Address No. = Times pushed)
Sets demand address.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Push confirmation button two times. Check demand address.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Push next page button one time. Returns to set mode.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Fig. 1
Setting of 5-bit cool/heat
address by DS1,2
Designate and set cool/heat
addresses 0-31 for each
operation mode switch unit.
No. 0
No. 7
No. 8
No. 15
No. 16
No. 31
: OFF : ON
Upper 2
bits DS2
C/H
LOWER
ADRESS
CENTRAL
NO.
DEMAND CONTROL ADRESS
Lower 3
bits DS1