Daikin RZQ125B7W1B [115/326] Condensation avoidance control

Daikin RZQ125B7W1B [115/326] Condensation avoidance control
ESIE05-03 Indoor Unit Functional Concept
Part 2 Functional Description 2–31
3
2
4
5
1
2.4 Condensation Avoidance Control
Purpose Avoid condensation on the swing flap when the most downward position of the swing flap (position 4)
is selected on the remote controller.
Applicable units This function is applicable for the FHQ units only.
Method The condensation avoidance control will function in the following operating modes:
P Cooling (automatic)
P Dry keep.
Method To avoid condensation on the swing flap, the condensation avoidance control is activated:
Stage Description
1 The fan operates in cooling mode with the blade in downward position (set on the remote
control).
2 After 30 min, the blade moves to a horizontal position.
3 After 1 h operation in horizontal position, the blade moves back to its downward position
for 30 min.
4 The unit operation is reset by:
P Changing the operating mode into “heating” or “fan
P Changing the air flow direction
P Turning the unit operation OFF and ON.