Daikin RZQ125B7W1B [96/326] Using conditions for remote controller thermostat

Daikin RZQ125B8V3B [96/326] Using conditions for remote controller thermostat
General Functionality ESIE05-03
2–12 Part 2 Functional Description
3
1
2
4
5
1.8 Using Conditions for Remote Controller Thermostat
Applicable The remote control thermostat is only available in wired remote controls.
Method The remote control sensor is standard disabled for sky-air units. The use of the remote control sensor
can be enabled by changing field setting 10(20)-2-02 to 10(20)-2-01.
Conditions The table below contains the condition in which the remote control thermostat is not used:
Cooling The diagram below shows the operation range of the set temperature / air suction temperature
combination in cooling operation:
Example Assuming the preset temperature above is 24°C, and the suction temperature has changed
from 18°C to 30°C (A --> F):
(This example also assumes there are several other air conditioners, the VRV system is off, and that
temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18°C to 23°C (A --> C).
Remote controller thermostat sensor is used for temperatures from 23°C to 27°C (C --> E).
Body thermostat sensor is used for temperatures from 27°C to 30°C (E --> F).
Condition The remote controller thermostat is not used when...
1 The remote controller thermostat malfunctions.
2 Group control is used.
3 The set temperature / air suction temperature combination is out of range. (See
below graph)
35
34
32
30
28
26
24
22
20
12 14 16 18
ABCD EF
20 22 24 26 28 30 32 34
TH1 = Ts - 3
TH1 = Ts - 1
TH1 = Ts + 1
TH1 = Ts + 3
Preset temperature
(Ts)
Range in which thermostat sensor
in remote controller can be used
Range in which
body thermostat sensor
can be used
Differential
Suction temperature (TH1)
ESIE05-03.book Page 12 Wednesday, April 6, 2005 4:09 PM