3.17 Stall Prevention (Time Lag) (L9)
Remote Controller
Display
L9
Method of
Malfunction
Detection
Malfunction is detected by converting the current flowing to power transistor into voltage with CT1 (DC
current sensor).
Inverter PC board detects the disorder of position signal.
Malfunction
Decision
Conditions
When compressor overload (except for when startup) is detected
When position signal is disordered
Supposed Causes
P Faulty compressor (lock)
P Pressure differential startup
P Faulty inverter
P The stop valve is left in closed.