Daikin RZQ125B7W1B [263/326] Outdoor unit check low pressure sensor

Daikin RZQ71B8V3B [263/326] Outdoor unit check low pressure sensor
ESIE05-03 Additional Checks for Troubleshooting
Part 3 Troubleshooting 3–115
33
4
5
1
5.9.5 Outdoor unit: Check Low Pressure Sensor
Measure the voltage (DC) between pins 2 and 3 of the connector.
(Blue)
Low pressure sensor
Red
Black
White
+5V
Outdoor unit PC board
Microcomputer
A/D input
Measure voltage (DC) here.
n
For RZQ71 models
(S2680)
(V3053)
P
H, PL
(Kg/cm²) MPa
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.5 1.5 2.5
-0.5
-0.5 0 1 2 3.534
Vdc
51.0
45.9
40.8
35.7
30.6
25.5
20.4
15.3
10.2
5.1
-5.1
00
Detected Pressure
Output voltage (V
L)
Low Pressure (P
L)
P
L = 0.57V-0.28
P
L: Low pressure (MPa)
V: Voltage (V)
P
L = Detected Presuure (Low side) MPa
V
L: Output voltage (Low side) Vdc
ESIE05-03.book Page 115 Wednesday, April 6, 2005 4:09 PM