Daikin RZQ125B7W1B [159/326] Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred

Daikin RZQ71B8V3B [159/326] Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred
ESIE05-03 Troubleshooting
Part 3 Troubleshooting 3–11
33
4
5
1
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Is the type of
remote controller wired or
wireless?
Does the fan rotate?
Is the filter soiled?
Is the
operation lamp
of indoor unit photo-sensing
section flashing?
Possible causes as follows:
Refrigerant overcharge
Mixing of air in refrigerant
system
Faulty pressure switch
Is there
any item disturbing
airflow?
Is the heat
exchanger
soiled?
Is the operation
lamp of remote
controller
flashing?
NO
NO
YES
NO
YES
YES
YES
YES
Wireless
YES
Heating: Indoor unit
Cooling: Outdoor unit
wired
[
]
(S1992)
NO
NO
Diagnose based on the error
code on remote controller
Malfunction of fan motor
Check the magnetic switch
and aux. switch for fan motor
Cleaning
Remove the disturbing item
Cleaning of the heat
exchanger
After vacuum drying, charge
correct amount of refrigerant
Check the pressure switch
ESIE05-03.book Page 11 Wednesday, April 6, 2005 4:09 PM