Daikin RZQ125B7W1B [162/326] Equipment operates but does not provide cooling

Daikin RZQ140B7W1B [162/326] Equipment operates but does not provide cooling
Troubleshooting ESIE05-03
3–14 Part 3 Troubleshooting
3
1
3
4
5
1.3.5 Equipment operates but does not provide cooling
Applicable Model All models of SkyAir series
Error Detection
Method
Error Generating
Condition
Possible Cause
P Overcurrent relay (for compressor)
P Compressor protection thermostat
P Overcurrent relay may act due to the following reasons
Lower voltage of power supply
Excess level of high pressure
Insufficient size of power cable
Malfunction of compressor
P Compressor protection thermostat may act due to the following reasons
Internal leakage of four-way valve (There is no difference between suction and discharge
temperature)
Insufficient compression of compressor
Incorrect refrigerant charge/leak
Faulty expansion valve
Insufficient circulation of refrigerant
P Malfunction of thermistors or thermistor out of position.
ESIE05-03.book Page 14 Wednesday, April 6, 2005 4:09 PM