Error Codes: Indoor Units ESIE05-03
3–52 Part 3 Troubleshooting
3
1
3
4
5
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Is the
capacity
setting adapter
plugged into X23A of the
indoor unit
PCB?
Is "AJ"
displayed on the
remote controller?
Plug a capacitor setting
adapter that matches the
capacity of the unit into X23A.
The malfunction was caused by
a missing capacity resistor.
Switch the power
supply off and
back on again.
Check if the capacity setting
adapter is plugged into X23A of
the indoor PCB.
Replace indoor
unit PCB.
No
No
Ye s
Ye s