Daikin RZQ125B7W1B [242/326] 94 part 3 troubleshooting

Daikin RZQ140B7W1B [242/326] 94 part 3 troubleshooting
Error Codes: Outdoor Units ESIE05-03
3–94 Part 3 Troubleshooting
3
1
3
4
5
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Is
the power
supply voltage between
220~240 VAC
±10%?
Check LED on
outdoor unit PC board. (Is the
voltage insufficient?)
NO
When the compressor is running,
measure the voltage between
+ and - of electrolytic capacitor
(C+, C-).
Other factors
Is the wiring correct?
Is the
measured voltage 220
VDC or more?
NO
YES
YES
YES
NO
NO
Field factors
Correct the wiring.
Monitor the voltage
(Instantaneous voltage drop)
Replace the inverter PC board.
ESIE05-03.book Page 94 Wednesday, April 6, 2005 4:09 PM