Error Codes: Outdoor Units ESIE05-03
3–66 Part 3 Troubleshooting
3
1
3
4
5
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
YES
NO
NO
YES
Is the
UVWN wiring
normal?
NO
YES
Is the
stop valve
open?
YES
NO
NO
Is high
pressure higher
than 2.6 MPa
at starting?
YES
NO
Check
and see
whether compressor is
short-circuited or
ground.
YES
Are
inverter output
voltages the same for
3 phases?
Does low or
high pressure vary
even instantaneously
when restarting
compressor?
Check the installation
conditions.
Open the stop valve.
Connect correctly.
Remedy the cause.
Replace the compressor.
Replace the inverter PC board.
Replace the compressor.
ESIE05-03.book Page 66 Wednesday, April 6, 2005 4:09 PM