Daikin RZQ125B7W1B [164/326] Equipment operates but does not provide heating

Daikin RZQ125B7W1B [164/326] Equipment operates but does not provide heating
Troubleshooting ESIE05-03
3–16 Part 3 Troubleshooting
3
1
3
4
5
1.3.6 Equipment operates but does not provide heating
Applicable Model All models of SkyAir series
Error Detection
Method
Error Generating
Condition
Possible Cause
P Excess charge of refrigerant
P Air intrudes into refrigerant system
P Faulty pressure switch
P Faulty magnetic switch for outdoor unit fan motor
P Faulty aux. relay for outdoor unit fan motor
P Soiled heat exchanger of outdoor unit
P There is an interfering item in air flow of outdoor unit
P Malfunction of outdoor unit fan
P Soiled air filter of indoor unit
P Soiled heat exchanger of indoor unit
P There is some interfering item in airflow of indoor unit
P Malfunction of indoor unit fan
ESIE05-03.book Page 16 Wednesday, April 6, 2005 4:09 PM

Содержание

Скачать