Daikin RZQ125B7W1B [222/326] Abnormal low pressure switch h4

Daikin RZQ125B7W1B [222/326] Abnormal low pressure switch h4
Error Codes: Outdoor Units ESIE05-03
3–74 Part 3 Troubleshooting
3
1
3
4
5
3.11 Abnormal Low Pressure Switch (H4)
Applicable model RZQ100~140
Remote Controller
Display
H4
Method of
Malfunction
Detection
P Check the continuity of LPS
P LPS is not operated when the low pressure is dropped under specific pressure (0.12MPa).
Malfunction
Decision
Conditions
When there is no continuity in the LPS during compressor start operating.
LPS is not operated when the low pressure is dropped under specific pressure (0.12MPa) during
compressor operating.
Supposed Causes
P Faulty LPS
P Disconnection in LPS harness
P Faulty connection of LPS connector
P Defect of outdoor unit PC board
P Refrigerant shortage
P Stop valve is not opened
P Defective expansion valve
P Clogged check valve
ESIE05-03.book Page 74 Wednesday, April 6, 2005 4:09 PM