ESIE05-03 Troubleshooting
Part 3 Troubleshooting 3–17
33
4
5
1
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Wait for a while.
No abnormality
No abnormality
Additional unit installation
should be considered
After vacuum drying, charge
correct amount of refrigerant.
Check each item
Check each item
Check each item
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
(S1995)
NO
Measure the temperature of
suction air and supply air.
Temperature difference =
Suction air temp. – Supply air
temp.
* Incorrect selection of model
* Affection of sunlight
* Affection of excessive fresh
air into room
Gas shortage possibly
generates trouble.
* Clogged air filter
* Soiled heat exchanger
* Malfunction of indoor fan
motor
(Refer error code “A6”)
* Refrigerant overcharge
* Soiled heat exchanger
* Short circuit of discharge air
* Disturbing item in air flow
* Malfunction of fan motor of
outdoor unit
(Refer error code “E7”.)
Does
the heat load
increase after installation
of the unit?
Is the unit in
defrost mode?
Is
the operation
current less than specified
level?
Does
indoor unit air flow
rate down?
Temperature
difference for heating
should be between 14
and 30˚C.
Is this
first starting after
installation?
* Insufficient compression of
compressor
* Insufficient circulation of
refrigerant
* Faulty expansion valve
Is the
level of high
pressure lower than
normal level?
This is normal. Heating
operation will be conducted
after 2 or 3 minutes.
See page 2-15 "Test Run
Control" for details.
ESIE05-03.book Page 17 Wednesday, April 6, 2005 4:09 PM