Daikin RZQ125B7W1B [198/326] 50 part 3 troubleshooting

Daikin RZQ125B7W1B [198/326] 50 part 3 troubleshooting
Error Codes: Indoor Units ESIE05-03
3–50 Part 3 Troubleshooting
3
1
3
4
5
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Is the limit
switch's transfer
connector correctly
connected?
Are
the connectors
correctly connected to
X29A and X14A
on the PC
board?
Does the swing
flap motor swing?
Does
continuity/
no continuity
reverse?
220-240 VAC?
Connect correctly.
Turn the power supply off
once and back on, and
check whether the swing
flap motor swings when
the power supply is turned
back on.
Turn the power supply off
once and back on, and
measure the output
voltage of connector X29A
when the power supply is
turned back on.
Disconnect X14A, turn the
power supply off once and
back on, and check if the
limit switch has continuity
when the power supply is
turned back on.
No
Connect correctly.
No
Replace the indoor
unit P.C.B.
Replace the swing
flap motor.
No
No
No
Ye s
Ye s
Ye s
Ye s
Ye s
ESIE05-03.book Page 50 Wednesday, April 6, 2005 4:09 PM