Daikin RZQ125B7W1B [239/326] Failure of capacity setting pj

Daikin RZQ140B7W1B [239/326] Failure of capacity setting pj
ESIE05-03 Error Codes: Outdoor Units
Part 3 Troubleshooting 3–91
33
4
5
1
3.21 Failure of Capacity Setting (PJ)
Remote Controller
Display
PJ
Method of
Malfunction
Detection
Check whether set value written in E
2
PROM (at factory) or set value of capacity setting adaptor (for
replacement) is the same as outdoor unit capacity.
Malfunction
Decision
Conditions
When the set value on E
2
PROM differs from the outdoor unit capacity or a capacity setting adaptor
except for PC board applicable models is installed. (Malfunction decision is made only when turning
the power supply on.)
Supposed Causes
P Improper set value of E
2
PROM
P Improper capacity setting adaptor
P Faulty outdoor unit PC board
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Make sure that the
combination of connected
capacity setting adapter
(CN26) is correct.
Is the
capacity setting
adapter (CN26)
connected to outdoor unit
PC board?
(Note)
Connect the adapter for the applicable model.
If incorrect, correct the combination.
NO
YES
(Note)
Capacity setting adapter is not connected at factory. (Capacity is written in E
²
PROM.) Capacity setting
adapter is required only when the PC board was replaced with spare PC board.
ESIE05-03.book Page 91 Wednesday, April 6, 2005 4:09 PM