Daikin RZQ125B7W1B [197/326] Swing flap motor malfunction lock a7

Daikin RZQ125B7W1B [197/326] Swing flap motor malfunction lock a7
ESIE05-03 Error Codes: Indoor Units
Part 3 Troubleshooting 3–49
4
5
1
3
2.6 Swing Flap Motor Malfunction / Lock (A7)
Error code A7
LED indications The table below shows the LED indications.
Error generation The error is detected by the limit switch when the motor turns.
When ON/OFF of the microswitch for position detection cannot be reversed eventhough the swing flap
motor is energized for a specified amount of time (about 30 seconds).
Causes The possible causes are:
P Failure of swing flap motor
P Failure of microswitch
P Failure of connector connection
P Failure of indoor unit PCB
Operation HAP (green) HBP (green)