Daikin RZQ125B7W1B [234/326] Malfunction of transmission system between control pcb and inverter pcb lc

Daikin RZQ125B7W1B [234/326] Malfunction of transmission system between control pcb and inverter pcb lc
Error Codes: Outdoor Units ESIE05-03
3–86 Part 3 Troubleshooting
3
1
3
4
5
3.18 Malfunction of Transmission system (Between Control PCB and Inverter PCB)
(LC)
Remote Controller
Display
LC
Method of
Malfunction
Detection
Checks and sees whether transmission between control and inverter PC board is carried out normally.
Malfunction
Decision
Conditions
When the transmission is not carried out in a specified period of time or longer
Supposed Causes
P Incorrect transmission wiring between control and inverter PC board/insufficient contact in wiring
P Faulty control and inverter PC board
P External factors (noise, etc.)
ESIE05-03.book Page 86 Wednesday, April 6, 2005 4:09 PM