Daikin RZQ125B7W1B [317/326] Removal of thermistor

Daikin RZQ125B7W1B [317/326] Removal of thermistor
ESIE05-03 Disassembly and Maintenance: Outdoor Units
Part 5 Disassembly and Maintenance 5–13
3
5
1
5
1.2.7 Removal of Thermistor
Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure
Step Procedure Points
P Remove the front and top
panels in accordance with the
Removal Procedure for
Outside Panel and others
P RZQ71~140B
1 In order to remove the
discharge pipe
thermistor, pinch the
mounting spring and pull
out this thermistor.
2 For the heat exchange
thermistor, pull the clamp
frontward and then
remove this thermistor.
3 In order to remove the
outdoor air thermistor,
pull out this thermistor
frontward and then slide it
to the right.
4
For the suction pipe
thermistor, pull this
thermistor frontward
and then remove it.
Discharge pipe thermistor
Thermistor
Suction pipe thermistor
Heat exchange thermistor
Mounting spring
Thermistor
Clamp
Outdoor air thermistor
Thermistor
Thermistor
ESIE05-03.book Page 13 Wednesday, April 6, 2005 4:09 PM