Daikin RZQ125B7W1B [166/326] Equipment discharges white mist

Daikin RZQ125B7W1B [166/326] Equipment discharges white mist
Troubleshooting ESIE05-03
3–18 Part 3 Troubleshooting
3
1
3
4
5
1.3.7 Equipment discharges white mist
Applicable Model All models of SkyAir series
Error Detection
Method
Error Generating
Condition
Possible Cause
P Humid installation site
P Installation site is dirty and with dense oil mists.
P Soiled heat exchanger
P Clogged air filter
P Malfunction of fan motor
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Did the trouble generate on
switching to heating mode after
complete of defrosting during
heating?
Continue unit operation.
It may be necessary to remove
the source of humid condition.
Dust or oil mists should be
removed.
Possible causes as follows
Clogged air filter
Malfunction of fan motor
Is
the room
temperature higher than
set value in cooling
operation?
Is
white fog coming out
from the unit?
Is the heat
exchanger of indoor unit
soiled?
Is the site
dusty or with dense
oil mist?
Is the
airflow rate too
small?
Normal
Remove the source of humid
condition.
Cleaning of heat exchanger is
necessary.
Remove the source of oil mist
or dust.
Cleaning of air filter
Check fan motor
(Refer error code “A6”)
Normal
(Fog is generated due to
defrosting operation)
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
(S1996)