Additional Checks for Troubleshooting ESIE05-03
3–104 Part 3 Troubleshooting
3
1
3
4
5
5.2 Outdoor unit: Checking the Installation Condition
Checking To check the installation condition, proceed as follows:
Change the
installation location.
No
Clean the heat
exchanger.
No
Change the
installation location
or direction.
No
Ye s
Ye s
Check the spaces for all air
passage around the suction
and discharge areas.
Check the outdoor ambient
temperature R1T.
This temperature must be
lower than 413˚C.
Change the
installation location.
Ye s
Does the
discharged air from
other outdoor units cause an
increase of the suction
temperature?
Is the
minimum space
rescpected?
Is the
heat exchanger
clean?
Ye s
Is there
enough
air flow?