Daikin RZQ125B7W1B [254/326] Checking the thermistors

Daikin RZQ71B8V3B [254/326] Checking the thermistors
Additional Checks for Troubleshooting ESIE05-03
3–106 Part 3 Troubleshooting
3
1
3
4
5
5.4 Checking the Thermistors
Thermistors If the cause of the problem is related to the thermistors, then the thermistors should be checked prior
to changing the PCB.
For more information about these thermistors, see:
P ’Wiring Diagrams’’ (outdoor units)
P “Functions of Thermistors” on page 2-4.
Overview of
thermistors
The table below contains an overview of the thermistors:
Checking To check the thermistors, proceed as follows:
Thermistor Description
Indoor R1T Suction air thermistor
R2T Heat exchanger thermistor
R3T Gas pipe thermistor
Outdoor R1T Ambient air thermistor
R2T Heat exchanger thermistor
R3T Discharge pipe thermistor
R4T Suction pipe thermistor
R5T Power module fin thermistor
Step Action
1 Disconnect the thermistor from the PCB.
2 Read the temperature and the resistor value.
3 Check if the measured values correspond with the values in the table on the next pages.
ESIE05-03.book Page 106 Wednesday, April 6, 2005 4:09 PM