3.3.8 Input Current Control
Outline Unlike the inverter current control, this function will monitor the overall input current and will restrict the
compressor upper limit operating frequency as to prevent activation of the circuit breakers.
Flow chart
Upper limit current The outdoor model type and the outdoor air temperature will determine the upper limit current value.
Upper limit compressor operating
frequency –1 step/6 sec
Normal operation
Upper limit compressor operating
frequency +1 step/2 min
Outdoor unit current
> upper limit current value
Outdoor unit current
upper limit
current value
Upper limit compressor operating
frequency = Maximum frequency
&
Outdoor unit current
upper limit current value
Outdoor unit current
>
upper limit current value
ABCD
RZQ71B8V3B 16.5 A 16.5 A 14.2 A 8.4 A
RZQ100~125B8V3B 24.0 A 24.0 A 22.0 A 10.0 A
RZQ100~140B7W1B 13.5 A 10.0 A 8.5 A 3.0 A
Overall current
(A)
Current (A)
Current (B)
Current (C)
Current (D)
Outside temperature (°C)
Ta