Daikin RZQ125B7W1B Сервис мануал онлайн [128/326] 607212

Daikin RZQ125B7W1B Сервис мануал онлайн [128/326] 607212
Outdoor Unit Functional Concept ESIE05-03
2–44 Part 2 Functional Description
3
1
2
4
5
Heating
Compressor
Pressure equalizing
control before
compressor start
Pressure
equalizing
start
Pressure
equalizing
complete
Starting
control
complete
Starting control
RZQ71: 73 Hz
RZQ100~140: 107 Hz
RZQ71: 480 pls
RZQ100~140:
65 pls
15s
ON
OFF
ON
ON (*)
Ta > 26°C
OFF
Ta < 26°C
Motorized valve
4 way valve
Previously ON
Previously OFF
Outdoor unit fan
ESIE05-03.book Page 44 Wednesday, April 6, 2005 4:09 PM