Daikin RZQ125B7W1B Сервис мануал онлайн [22/326] 607212

Daikin RZQ125B7W1B Сервис мануал онлайн [22/326] 607212
Introduction ESIE05-03
xii
3
1
4
5
Charging cylinder
P Specifications
Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
P Differences
The cylinder can not be used for mixed refrigerant since mixing ratio is changed during charging.
When R410A is charged in liquid state using charging cylinder, foaming phenomenon is
generated inside charging cylinder.
Weigher for
refrigerant charge
P Specifications
•High accuracy
TA101A (for 10-kg cylinder) = ± 2g
TA101B (for 20-kg cylinder) = ± 5g
Equipped with pressure-resistant sight glass to check liquid refrigerant charging.
A manifold with separate ports for HFCs and previous refrigerants is equipped as standard
accessories.
P Differences
Measurement is based on weight to prevent change of mixing ratio during charging.
Charge mouthpiece
P Specifications
For R410A, 1/4" 5/16" (2min 2.5min)
Material is changed from CR to H-NBR.
P Differences
Change of thread specification on hose connection side (For the R410A use)
Change of sealer material for the HFCs use.
Can not be used
ESIE05-03.book Page xii Wednesday, April 6, 2005 4:09 PM

Содержание