Daikin RZQ125B7W1B Сервис мануал онлайн [286/326] 607212

Daikin RZQ71B8V3B Сервис мануал онлайн [286/326] 607208
Field settings ESIE05-03
4–22 Part 4 Commissioning and Test Run
3
1
4
5
This drawing shows the position of jumper JX5 on PCB A1P.
DIP switches The table below contains the DIP switch field settings.
BS The table below contains the BS field setting.
DIP
switch
Label on PCB Function Details
DS1-1 ON/OFF Switch emergency operation outdoor unit ON/OFF. See page 2-6.
DS1-2 Cool / Heat Select cooling / heating emergency operation. See page 2-6.
DS1-3 ON/OFF Test purposes only. Keep factory setting “OFF”.
DS1-4 ON/OFF Test purposes only. Keep factory setting “OFF”.
BS Label on PCB Function Details
BS BS1 Cooling / fan only: Pump down
Heating: Forced defrosting function
See page 2-18.
See page 2-6.