Gree HOME GMV Инструкция по эксплуатации онлайн [100/367] 48267

Gree HOME GMV Инструкция по эксплуатации онлайн [100/367] 48267
Dc Inverter VRF plus Water Heater Solution Service Manual CONTROL
96
Fig. 3.1 illustrates the simple installation process of wired controller. Care shall be taken to the
following points:
1. Before installation, firstly cut off the power supply to the cables buried in the mounting hole of
wall. Do not operate on live components during the entire installation process.
2. Pull out the 4-cord twisted wire from the mounting hole on wall and insert this wire into square
hole behind the base plate of wired controller.
3. Attach the base plate of wired controller onto the wall and fix it to the mounting hole of wall with
screws M4X25.
4. Finally, insert the 4-cord twisted wire into the slot on wired controller and clamp the panel of
wired controller to the base plate.
CAUTION:
To avoid malfunction of air conditioner due to electromagnetic interference, make sure to take
special care when carrying out the following connections:
1. The signal wire and distribution wire (communication) of the wired controller shall be separated
from the power cables and indoor / outdoor wires, with minimum spacing higher than 20cm;
otherwise the communication of machine might become abnormal.
2. If the air conditioner unit is installed at a place likely subject to electromagnetic interference, the
signal wire and distribution wire (communication) of the wired controller must be shielded twisted
wire.
4.2.6 Connection of Communication Wire
No. 1 2 3 4 5
Name Socket housing
installed in wall
Base plate
of controller
Screw M4X25 Control
Panel
Screw
ST2.2X6.5
Fig. 3.1 Installation Schematics of Wired Controller