Gree HOME GMV [186/367] Connection of branch pipe the y type branch pipe is installed with additional tube the purpose is to adjust the different pipe diameters if the pipe size selected on site is different from the size of branch connector please use the pipe cutter to cut from the middle of different connection pipes and remove the burrs then insert the copper pipe to appropriate depth the branch pipes from gree are all provided with positioning mark

Gree HOME GMV [186/367] Connection of branch pipe the y type branch pipe is installed with additional tube the purpose is to adjust the different pipe diameters if the pipe size selected on site is different from the size of branch connector please use the pipe cutter to cut from the middle of different connection pipes and remove the burrs then insert the copper pipe to appropriate depth the branch pipes from gree are all provided with positioning mark
Dc Inverter VRF plus Water Heater Solution Service Manual INSTALLATION
182
Connection of branch pipe
The Y-type branch pipe is installed with additional tube. The purpose is to adjust the different pipe
diameters. If the pipe size selected on site is different from the size of branch connector, please
use the pipe cutter to cut from the middle of different connection pipes and remove the burrs. Then,
insert the copper pipe to appropriate depth. The branch pipes from Gree are all provided with
positioning mark.
The connection method that copper pipe is in couple with a smaller branch pipe shall not be used.
Copper pipe shall not be inserted too much for connection with branch pipe.
Copper pipe
Branch pipe
Cut from the middle of coppe
r
pipe as needed
Copper pipe
Branch pipe
Correct connection
Wrong connection
Copper pipe
Correct connection
Wrong connection
Branch pipe