Dc Inverter VRF plus Water Heater Solution Service Manual PRODUCT
14
4 PRODUCT DATA
4.1 Product data of outdoor
Item
Model
GMV-Pds100
W/Na-K
GMV-Pds12
0W/Na-K
GMV-Pds
140W/Na-
K
GMV-Pds
160W/Na-
K
GMV-Pds
224W/Na-
M
GMV-Pds
280W/Na-
M
Rated Cooling Capacity kW 10 12 14 16 22.4 28
Rated Heating Capacity kW 11 14 15.4 17.6 25 31.5
Rated Water Heating kW 5 5 8 8
12kw
(default),
12~20kW
12kw
(default),
12~30kW
Hot water L/h 107 107 172 172 258~500 258~650
Supply Water Temp.
50 (default), adjustable between 35-58
Noise dB (A) 56 56 58 60 58 58
Comprehensive
Cooling Performance
Coefficient(IPLV) W/W 4.2 4.2 4.2 4.2 3.6 3.6
Comprehensive
Energy-Efficiency Ratio W/W 6.0 6.0 6.6 6.6 6.0 6.4
Compressor
DC Inverter Dual-rotor
Type Compressor x 1
DC Inverter
s
croll×1+constant
speed scroll ×1
R410A Charge Volume kg 5 5 7 7 15 16
Power Supply
220-240V-1Ph-50Hz 380-415V-3Ph-50Hz
Rated
Power
Cooling kW 4.5 5 5.5 5.9 6.82 7.52
Heating kW 3.8 4.2 4.9 5.3 6.97 7.7
Water Heating kW 2 2 2.86 2.86 8 10.7
Rated
current
Cooling A 20.2 23 25 26.8 11.7 13.4
Heating A 18.1 19.1 22.3 24.1 11.4 13.76
Water Heating A 9 9 12.8 12.8 13.1 19.1
Dimension Size (mm) (W×D×H) 950×340×1250
930×770×1670
Dimensions of Package 1110 ×450×1370 1010 ×850×1850
Connect
ion Pipe
Liquid Pipe (Air
Conditioner) mm φ9.52 φ9.52 φ9.52 φ9.52
φ9.52 φ9.52
Gas Pipe (Air
Conditioner) mm φ19.05 φ19.05 φ19.05 φ19.05
φ22.2 φ22.2
Liquid Pipe (Hot
Water) mm φ12.7 φ12.7 φ12.7 φ12.7
φ15.9 φ15.9
Gas Pipe (Hot
Water) mm φ15.9 φ15.9 φ15.9 φ15.9
φ19.05 φ19.05
Connection mode Flared connection
Net weight/Gross Weigth kg 105/115 105/115 115/125 115/125 265/285
Note:
The comprehensive energy-efficiency ratio is (the cooling capacity obtained by indoor unit + Heating capacity
of hot water / Power consumption. Example: ECOP= (8.0kW+8.0kW+2.86kw)/2.86 kW=6.6
The performance data of the air conditioner unit are measured under rated working conditions.
The R410A charge volume above refers to the charge volume in the outdoor unit at the time of shipment.
During installation, the charge volume of additional refrigerant shall be calculated according to the pipe length
and the configuration of indoor units.
The data above shall be based on the nameplate.