Gree HOME GMV [235/367] Dc inverter vrf plus water heater solution service manual servicing

Gree HOME GMV [235/367] Dc inverter vrf plus water heater solution service manual servicing
Dc Inverter VRF plus Water Heater Solution Service Manual SERVICING
231
Overcurrent occurs in operation, i.e. the indicator will display the current protection just after startup.
Yes
Yes
Yes
No
No
Use DC level to monitor P &
N voltage of the
module
Check the indoor units
for matching
Correct the match of indoor units to
allowable capacity
Check if the charge volume
is too high
The charge volume is too
high
A
djust to allowable range stated
in the specifications
DC capacitor damaged.
Replace it
Within 135%
Voltage stabilized 252-330V,
with no fluctuation over 10V
Compressor damaged;
module damaged
Yes
Yes
Yes
No

Содержание