Dc Inverter VRF plus Water Heater Solution Service Manual INSTALLATION
192
full-load cooling mode. Open V
H
and discharge air in the hose. The high pressure end of pressure
gauge is connected to the refrigerant filling nozzle on the small valve of outdoor unit. Open V
L
and
charge gas state refrigerant into the gas pipe until required charging amount is reached.
c.Observe electronic balance or spring balance. When required amount is reached, the valve shall
be closed very quickly and then source valve on the refrigerant valve shall be shut off.
d. The amount of charging refrigerant shall be recorded.
Refrigerant charge shall be recorded as per the following table.
Unit Mark Amount of charging refrigerantKg
Unit 1
Unit 2
………
Unit n