Dc Inverter VRF plus Water Heater Solution Service Manual INSTALLATION
181
See below for the welding size of copper pipe:
A
D
Outer diameter of pipe D
(mm)
Min. insert depth B
(mm)
Clearance
A-D
ф6.35 6
0.050.21
ф9.52, ф12.7 7
ф15.8 8
0.050.27
ф19.05, ф22.2, ф25.4 10
ф28.6, ф31.8 12
0.050.35
≥ф35 14
If the mounting clearance is too large, the diameter of coarse pipe may be reduced to an
appropriate value to according to applicable specifications.
3Installation of branch pipe
The branch pipe plays the function to divert the refrigerant flow. Therefore, the selection and
installation of branch pipe is very important to the operation of multi-unit. Based on correct
selection of branch pipe, the branch pipe must be installed according to installation specifications.
Connection schematics for Y-type branch pipe
The connection of Y-type branch pipe is as shown below. The inlet is connected to outdoor unit or
previous branch; the outlet is connected to indoor unit or next branch.
Installation specifications for branch pipe
Placement of branch pipe
The branch pipe can only placed horizontally. Meanwhile, two branch pipes must be on the same
plane. The spacing between two branch pipes must be over 800mm, the spacing between two
bends must be over 800mm, and the spacing between branch pipe and bend point must also be
over 800mm.
Site pipe
Site pipe
Inlet
Outlet 1
Y
-type Manifold Pipe
To other manifold
pipe or indoor unit
Ou
t
door unit
Outlet 2
A
-A Schematics B-B Schematics
Within 30°
Within 30°