Dc Inverter VRF plus Water Heater Solution Service Manual INSTALLATION
173
Units with capacity between 20kW and 60 kW
Allowable
Vl
Fitting Pipe
Total length (actual length) of fitting pipe
300m
L
0+
L
1
+L
2
+L
3
+L
4
+L
5
+L
6
+a+b+…+i+j
Length of farthest
fitting pipem
Actual length
100m
L
1
+L
3
+L
4
+L
5
+L
6
+j
Equivalent length
125m
length from the first branch to the furthest
ii
L( )
40m
L
3
+L
4
+L
5
+L
6
+ j
Height difference
between outdoor unit
and indoor unit
Outdoor unit at
50m
——
Outdoor unit at
l
40m
——
Height difference between indoor unitsm
15m
——
length from outdoor unit to Hydro Unit 10m L0
length from Hydro Unit to water tank 10m L9
The equivalent length is designed as per one Y-Type manifold pipe every
0.5m
The 1st
manifold
Indoor Unit
b
Outdoor Unit
The equivalent length of the farthest pipe from the 1st manifold: L≤20m
c
Equivalent length of farthest pipe: L60m
Indoor unit
d
a
Circulating Water Pipe
Pressure
water tank
Refrigerant Pipe
Height difference between indoor unit and outdoor unit
Height difference between
indoor units:
h≤10m
H≤25m
Hydro unit
wired controller
Hydro
unit