6.2 Explanation of Flowchart
When connected to power, the indoor and outdoor units start to work. When working under
cooling mode, the low-temperature and low-pressure refrigerant gas from the heat exchanger of
each indoor unit will collect and be suctioned by compressor, where it will be compressed into
high-temperature high-pressure gas. After that, the gas will enter into the outdoor heat exchanger,
where it will exchange heats with the outdoor air and become refrigerant liquid. Via Y-type
Branching pipe or Branching collection pipe, the liquid will flow into each indoor unit. The liquid will
be decreased of the pressure and temperature by throttling element. After that, the liquid will enter
into the indoor heat exchanger, where it will exchange heats with the air to be regulated in the
room and thus become low-temperature low pressure refrigerant gas. The process is cycled
repeatedly to achieve the purpose of cooling.
When working under heating mode, the 4-way valve AB will be activated, so that the
refrigerant will circulate in reverse to the cooling process. The refrigerant gives out heats in indoor
heat exchanger (Under specific conditions, the electric heating elements will start to work and give
out heats). In the outdoor heat exchanger, the refrigerant will absorb heat to perform heat pump
heating cycle, so as to achieve the purpose of heating.
When working under heating and hot water generation mode, the 4-way valve AB will be
activated, so that the refrigerant will give out heats in indoor heat exchanger and hydro indoor unit,
but absorbing heats in outdoor heat exchanger for heat pump heating and hot water generation
cycle, thus to achieve the purpose of both heating and hot water generation.
When working under hot water generation mode, the 4-way valve B will be activated, so that
the refrigerant will give out heats in hydro indoor unit, but absorbing heats in outdoor heat
exchanger for heat pump heating and hot water generation cycle, thus to achieve the purpose of
hot water generation.
When working under cooling and hot water generation mode, the 4-way valve B will be
activated as needed, in which case the refrigerant will give out heats in hydro indoor unit, but
absorbing heats in indoor heat exchanger for cooling heating and hot water generation cycle.
Under this mode, test may be done for complete recycling of the heats. But when the water
temperature is very high, only a part of heats can be recycled. The system may identify according
to reliable working range. In this way, the machine realizes the purpose of both cooling and hot
water generation.