Gree HOME GMV Инструкция по эксплуатации онлайн [140/367] 48267

Gree HOME GMV Инструкция по эксплуатации онлайн [140/367] 48267
Dc Inverter VRF plus Water Heater Solution Service Manual INSTALLATION
136
Never remove any packaging materials.
As shown, insert two ropes through the square holes on the machine and protect the machine with
batten and corrugated paper.
不得拆去木头框
架与塑料绑带
将绳索捆在厚度超过15毫
米的木条板和波形纸板上
不要在这块板上施加
任何力(两面)
将绳索从方形孔中穿过
绳索与机器之间的角
度要大于60度
绳索
During lifting, the position of ropes is as shown below.
Move the lower wood frame of the packaging box away and lift the unit to correct position.
方形孔
绳索
正确
方形孔
绳索
错误
5.1.1 Cautions for installation of side outdoor unit
To ensure good operation of the air conditioner, the selection of installing position must be in
accordance with the following principles:
The outdoor unit shall be so installed that the air discharged out of the outdoor unit will not
flow back and that enough space shall be maintained around the machine for repair.
The installing position shall be in good ventilation, so that the machine can breathe and
exhaust enough air. Ensure that there is no obstruction at the inlet and outlet of the machine.
If any, please remove the obstructions blocking the air inlet and outlet.
Also ensure that the outlet air and noise from the air conditioner will not affect the neighbors.
The outdoor unit must be lifted by using the designated lift hole. During lifting, take care to
protect the air conditioner and avoid knocking the metal parts, thus to prevent rusting in the
future.
Avoid direct sunshine as it might be.
The installing position must be able to drain the rainwater and the water generated from
defrosting.
The installing position must ensure that the machine will not be buried in the snow or affected
by the wastes or oil mist.
To meet the noise and vibration requirements, the outdoor unit shall be installed by using
rubber damping pad or spring damper.
The installing dimension shall comply with the installation requirements in these instructions.
The outdoor unit must be fixed at the installing position.
The installation shall be done by specialist technicians.
5.1.2 Cautions for installation of up outdoor unit
To ensure good operation of the air conditioner, the selection of installing position must be in
accordance with the following principles:
The outdoor unit shall be so installed that the air discharged out of the outdoor unit will not
flow back and that enough space shall be maintained around the machine for repair.
The installing position shall be in good ventilation, so that the machine can breathe and
Never remove the wood
frame and plastic straps.
The angle between rope
and machine shall be
higher than 60º.
Tie the ropes the batten and
corrugated paper with a
thickness not over 15mm.
Do not apply any
force to this board
(both sides).
Insert the ropes through
square hole.
Rope
Rope
Rope
Square hole
Square hole
Correct
Wrong