Gree HOME GMV Инструкция по эксплуатации онлайн [141/367] 48267

Gree HOME GMV Инструкция по эксплуатации онлайн [141/367] 48267
Dc Inverter VRF plus Water Heater Solution Service Manual INSTALLATION
137
exhaust enough air. Ensure that there is no obstruction at the inlet and outlet of the machine.
If any, please remove the obstructions blocking the air inlet and outlet.
Also ensure that the outlet air and noise from the air conditioner will not affect the neighbors.
The outdoor unit must be lifted by using the designated lift hole. During lifting, take care to
protect the air conditioner and avoid knocking the metal parts, thus to prevent rusting in the
future.
Avoid direct sunshine as it might be.
The installing position must be able to drain the rainwater and the water generated from
defrosting.
The installing position must ensure that the machine will not be buried in the snow or affected
by the wastes or oil mist.
To meet the noise and vibration requirements, the outdoor unit shall be installed by using
rubber damping pad or spring damper.
The installing dimension shall comply with the installation requirements in these instructions.
The outdoor unit must be fixed at the installing position.
The installation shall be done by specialist technicians.
5.2 Selection of Installation Site
The place with no residual air
The place where the accessories can be securely fixed
The place where the air will not obstruct the water inlet pipe or water outlet pipe
The place that goes beyond the heating range of other heat sources
The place where the wastewater can be safely drained
The place where the noise and hot air will not affect the neighbors
The place where the snow will not be piled
The place where the water outlet pipe will not be blown by strong wind
Notes:
Do not use guardrail on four sides. Leave 1m at least above the machine.
In case of short-circuit risk, please install an adaptor changeable in air direction.
To avoid short circuiting, please provide adequate suction space when multiple machines are
to be installed.
In the region with snow, the machine shall be installed in a frame or beneath the snow guard,
thus to prevent snow piling on the machine.
Do not install the equipment in a region where any inflammable gas might leak.
The snow guard and other devices shall be designed and installed by the user.