Dc Inverter VRF plus Water Heater Solution Service Manual INSTALLATION
200
¾ The diameter of drainage pipe shall be equal to or higher than the diameter of connection pipe
(PVC pipe) (exclusive of the rise section).
¾ The drainage pipe shall be short and has a down gradient of 1/100 at least, thus to avoid air
bag.
¾ If the inclination of the drainage hose is insufficient, drainage rise pipe shall be mounted.
¾ The installing height of drainage rise pipe shall be less than 280mm.
¾ The drainage rise pipe shall be in right angle to the unit and the distance to the unit shall not
exceed 300mm.
¾ The inclination of included drainage hose shall be within 75mm, so that the drainage insert will
not bear excessive force.
¾ To prevent the drainage hose from dropping downward, hanger rods shall be erected every
1.0~1.5m.
¾ Use the included drainage hose and clamp. Insert the drainage hose to the drainage port and
tighten the clamp.
¾ For thermal insulation, wrap the big sponge to the drainage hose clamp.
¾ The indoor drainage hose shall be thermally insulated.
Drainage hose
(accessory)
Below 500mm
Below 75mm
Correct
Hanger rod Gradient over 1/100
Incorrect
Roof
Drainage rise
p
i
p
e
Ceiling
Clamp (accessory)
Below 280mm
Hanger seat
Within 300mm
Below 500mm
Drainage hose
(accessory)