Gree HOME GMV Инструкция по эксплуатации онлайн [42/367] 48267

Gree HOME GMV Инструкция по эксплуатации онлайн [42/367] 48267
Dc Inverter VRF plus Water Heater Solution Service Manual PRODUCT
38
4.2.4Floor Ceiling Type
Model GMV(L)-R28Zd/Na-K GMV(L)-R36Zd/Na-K
GMV(L)-R50Zd/Na-
K
Cooling Capacity
kW
2.8
3.6 5.0
Btu 9554 12284 17061
Heating Capacity
kW
3.2
4.0 5.8
Btu 10919 13649 19790
Air Flow Rate
m3/h 550 600 700
CFM
324
353 412
Sound Pressure Level (H/L) dB(A) 43/- 44/- 50/-
External Static Pressure Pa / / /
Power Supply 220-240V-1Ph-50Hz 220-240V-1Ph-50Hz 220-240V-1Ph-50Hz
Fan Motor
Output kW 0.01 0.01 0.04
Running
Current
A 0.1 0.1 0.4
Connectin
g Pipes
Gas Pipe
mm Φ9.52 Φ12.7 Φ12.7
inch Φ3/8 Φ1/2 Φ1/2
Liquid Pipe
mm Φ6.35 Φ6.35 Φ6.35
inch
Φ1/4 Φ1/4 Φ1/4
Connection Method Flare Connection Flare Connection Flare Connection
Drain Pipes
External Dia. × Thickness
mm Φ17×1.75 Φ17×1.75 Φ17×1.75
Unit Dimensions
(W×D×H)
mm 840×238×695 840×238×695 840×238×695
Package Dimensions
(W×D×H)
mm 1035×295×805 1035×295×805 1035×295×805
WeightNet/Gross kg 28/37 28/37 28/37
Notes:
Refer to the product nameplate for parameters and specification of the unit;
The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the
cooling only units does not have any parameters of performing heating;
The sound level is tested under circumstance of semi-anechoic chamber; the value of noise could be a
little higher in actual operation.