The Digital Controller For Multiscroll Chillers ESIE06-05
2–28 Part 2 – Functional Description
3
1
2
4
5
Possible settings F1*/ F2*:
For standard fans:
Inverter fans (OPIF or OPLN)
000% : percentage of fan output
2.8.2 Compressor settings
Compr. Lead-Lag This screen allows modification of the compressor lead-lag settings:
Possible settings MODE:
Compr. Cap. Limit This screen allows modification of the compressor capacity limitation settings.
OFF : All fans off
L:Low speed
M:Medium speed
H:High speed
PRIORITY:
The user can select the sequence of the compressors to start.
example:
C11 > C12 : compressor 1 will start before compressor 2
AUTO : The compressor lead-lag according to the running hours of
the compressors
COMPR.LEAD-LAG
C11>C12>C21>C22
_v
MODE:PRIORITY
PRIORITY:
COMPR.CAP.LIMIT
C11:OFF
C21:OFF
_^
C22:OFF
C12:OFF
MODE:LIMIT SETTING
SET: