Overview of Fault Indications and Safeties ESIE06-05
3–6 Part 3 – Troubleshooting
3
1
3
4
5
1.4 Overview of Unit Safeties
Introduction This section provides useful information for diagnosing and correcting certain troubles which may
occur in the unit.
Before starting the troubleshooting procedure, carry out a thorough visual inspection of the unit and
look for obvious defects such as loose connections or defective wiring.
When carrying out an inspection on the supply panel or on the switch box of the unit, always
make sure that the circuit breaker of the unit is switched off.
Unit safety
overview
Unit Safety
description
OAE : FLOW HAS STOPPED
Purpose:
To prevent that chiller start up without flow.
To stop chiller when there is no flow.
MESSAGE SAFETY MENU
UNIT SAFETY
0AE:FLOW HAS STOPPED
0AE:PUMPINTERLOCK
0A4:FREEZE UP
0A9:EEV PCB COMM ERR
0A9:EEV PCB ERR
0C9:INL SENSOR ERR
0CA:OUT SENSOR ERR
0H9:AMB T SENSOR ERR
0U4:EXTPCB COMM.ERR
0U4:MAINPCB COMM.ERR
0U5:PCB COMM.PROBLEM
Symptom: Flowswitch is activated
POSSIBLE CAUSES CORRECTIVE ACTION CONSEQUENCE
No water flow for 5 seconds
continuously or too low water
flow.
Check the water pump filler
and the water circuit for
obstructions.
Unit switched off.
RESET : After finding the cause, the flowswitch is reset automatically, but the controller still needs
to be reset.