Daikin EWYQ230DAYN [457/524] Compressor electrical connections and wiring

Daikin EWYQ210DAYN [457/524] Compressor electrical connections and wiring
ESIE06-05 Compressor electrical connections and wiring
Part 3 – Troubleshooting 3–57
33
4
5
1
Part 3
11 Compressor electrical connections and wiring
11.1 Electrical connections for SJ161
Electrical power is connected to the compressor terminals by diameter 4,8 mm (3/16”) screws. The
maximum tightening torque is 3 Nm. Use a 1/4” ring terminal on the power leads.
11.2 Electrical connections SJ180
Electrical power is connected to the compressor terminals by diameter 4,8 mm (3/16”) screws. The
maximum tightening torque is 3Nm. Use a 1/4” ring terminal on the power leads.
The protection rating of the terminal box is IP54.
11.3 Electronic protection module wiring
The motor protection module comes preinstalled within the terminal box and has pre-wired thermistor
connections. The module must be connected to a power supply of the appropriate voltage.
Terminal box
Power supply
ø 29 mm knockout
Motor Protection
12
14
11
N
2
1
M odule
L1
Discharge gas thermostat
Cover holding
screw (x2)
Torque:
2.2 Nm.
Terminal box
Power supply
Faston 1/4" tabs
Belt type
heater
Protection module
power supply
Discharge gas pipe

Содержание

Скачать