Daikin EWYQ230DAYN [264/524] Advanced

Daikin EWAQ260DAYN [264/524] Advanced
The Digital Controller For Multiscroll Chillers ESIE06-05
2–38 Part 2 – Functional Description
3
1
2
4
5
Settings:
2.8.10 Advanced
Advanced This screen allows modification of the advanced password settings.
MODE (Parameter can be set
on each unit)
:
NORMAL: Unit is part of the DICN setup
STANDBY: A unit with mode “STANDBY”
will only be able to loadup if:
-a safety is present on a unit in
the DICN setup.
OR
-all other units are on 100%
capacity (possible to disable).
In case more than 1 unit has
“STANDBY” setting, the
actual standby will be
calculated (based on running
hours).
Remark: all units can be put on
“STANDBY”, in which case the
DICN will calculate which unit will
be the actual standby.
:
DISCONN. ON/
OFF
A unit with mode “DISCONNECT
ON/ OFF” can be put on/off
independently from the DICN
on/off status (setpoint & other
network parameters are still
controlled on DICN level) and
unit can be put in manual mode.
OFFSET : The offset time defines the target difference in running
hours between one unit and another unit.
PUMP ON IF : UNIT IS ON: pump of individual unit will run if
unit is on
COMPR ON: pump of individual unit will only
run if the compressor of that unit
is on
_v
PASSWORD NEEDED FOR:
SETPOINT MENU:Y
UNIT ON/OFF:Y
ADVANCED