Daikin EWYQ230DAYN [294/524] Runn hours

Daikin EWYQ230DAYN [294/524] Runn hours
The Digital Controller For Multiscroll Chillers ESIE06-05
2–68 Part 2 – Functional Description
3
1
2
4
5
2.15.4 Pump
Pump Control This screen allows modification of the manual pump control and the pump running hours.
Settings:
Remark: When the manual pump control is activated, the pump will switch OFF (disable manual
control) when you leave the Service menu.
Pump Control with
low water
temperature
This screen allows modification of the pump control with low water temperatures when unit is switched
off.
Settings:
Remark: This screen is only visible when no heater tape is installed.
MAN. PUMP : Manual switching on pump 1 or 2
RUNN. HOURS RHP1/
P2
: Running hours of pump 1 and pump 2. When the software is
updated or the PCB is replaced, these running hours have to be
entered in the new configuration.
_
MAN.PUMP:OFF 2ND:OFF
RUNN. HOURS
RHP1:00000hP2:00000h
PUMPCONTROL
OFF : Pump function is disabled (default setting)
ON : Pump function is enabled.
_
IF UNIT OFF AND LOW
WATER TEMP THEN PUMP
:OFF
PUMPCONTROL