Daikin EWYQ230DAYN [302/524] Eev control

Daikin EWYQ100DAYN [302/524] Eev control
The Digital Controller For Multiscroll Chillers ESIE06-05
2–76 Part 2 – Functional Description
3
1
2
4
5
EEV Fan Up/Down
Control
This screen allows modification of the EEV fan up/down control.
Settings:
EEV Low Pressure
Control
This screen allows modification of the EEV Low Pressure Control in cooling mode.
Settings:
FAN DOWN PLS
: When the Fan step goes DOWN, immediately close EV with 20
pulses.
FAN UP PLS
: When the Fan step goes UP, immediately open EV with 20 pulses.
_
FAN UP PLS:200pls
FAN DOWN PLS:050pls
EEV CONTROL
LP PR. SETP COOL : When the LP drops below LP PR. SETP COOL (2.3 bar)
add 200 pulses to the actual electronic expansion valve position.
LP PR. RESET COOL : When the LP rises back above LP PR. RESET COOL (3.0 bar)
reset the function and stop adding additional pulses.
LP ADD COOL : Additional pulses that will be added when the low pressure is
below the low pressure prevention setpoint in Cooling mode.
_
LP PR.RESET COOL:3.0b
LP PR.SETP COOL:2.3b
EEV CONTROL
LP ADD COOL:0200pls