ESIE06-05 The Digital Controller For Multiscroll Chillers
Part 2 – Functional Description 2–77
3
2
4
5
1
EEV Low Pressure
Control
This screen allows modification of the EEV Low Pressure Control in heating mode.
Settings:
LP PR. SETP HEAT : When the LP drops below LP PR. SETP HEAT (2.3 bar)
add 200 pulses to the actual electronic expansion valve position.
LP PR. RESET HEAT : When the LP rises back above LP PR. RESET HEAT (3.0 bar)
reset the function and stop adding additional pulses.
LP ADD HEAT : Additional pulses that will be added when the low pressure is
below the low pressure prevention setpoint in Heating mode.
_^
LP PR.RESET HEAT:3.0b
LP PR.SETP HEAT:2.3b
EEV CONTROL
LP ADD HEAT:0200pls