The Digital Controller For Multiscroll Chillers ESIE06-05
2–92 Part 2 – Functional Description
3
1
2
4
5
Fan Overcurrent
Setting For V2.2
This screen allows modification of the fan overcurrent safety for software version V2.2.
Settings:
Unit Status during
Safety
This screen allows modification of the unit status when a safety is active.
Settings:
FAN OVERC.:
WARNING: When a fan overcurrent occurs, a warning will be displayed,
but the unit will continue operation.
SAFETY: When a fan overcurrent occurs, a safety will be displayed and
the circuit will be switched off.
FREEZE UP OW:
Freeze up safety on outlet water temperature
DIS&SAF Use the same logic as the freeze up safety on refrigerant gas
temperature (second time in 30 min
alarm).
DISABLE Same function as software version V2.1. Unit will shut down
on freeze up but will restart automatic and no alarm is
displayed.
_ SAFETY
FAN OVERC.:WARNING
FREEZE UP OW:DIS&SAF
IF UNIT SAFETY THEN PUT UNIT OFF:
YES: Normal function. The after safety unit has to be restarted.
NO: Used with D-bacs control. When the unit switches off the after
safety, there is a possibility that the safety can not be seen by
the D-bacs control.
_ SAFETY
IF UNITSAFETY THEN
PUT UNIT OFF:NO