Daikin EWYQ230DAYN [308/524] Ai1 type 0 20ma

Daikin EWYQ210DAYN [308/524] Ai1 type 0 20ma
The Digital Controller For Multiscroll Chillers ESIE06-05
2–82 Part 2 – Functional Description
3
1
2
4
5
Changeable Digital
Output and
Analogue Input
This screen allows modification of the changeable digital output and analogue inputs.
Settings:
Remark: The digital input will close when a 5 V DC signal is given to the controller.
DO6 : To set the digital output 6
AI1 : To set the analogue input 1
AI1 TYPE : To set the type of the analogue input 1
When programming this digital output or analogue input, check the field wiring to see if the output
or analogue input has been installed correctly.
The changeable analogue inputs can be programmed as analogue inputs OR as digital inputs.
1. Select the analogue input status
2. Specify the type of the used signal
Possible settings analogue inputs
None
Status
Floating setpoints
Temperature
Possible settings analogue input as digital input
DI STATUS
DI REM. COOL / HEAT
DI CAP LIM 25% / 50% / 75%
DI CAP LIM SET
DI FREE COOLING
_ CHANG. INP/OUTPUTS
DO6:NONE (OPEN)
AI1:NONE
AI1 TYPE:0-20mA