Daikin EWYQ230DAYN [390/524] Password function

Daikin EWYQ230DAYN [390/524] Password function
Functional Control for a Standalone Unit ESIE06-05
2–164 Part 2 – Functional Description
3
1
2
4
5
3.20 Password Function
Introduction A user password can be chosen, in the user password menu, to protect the user settings.
In the user advanced menu it can be chosen whether a password is needed to change the setpoint.
In the service/safety menu you can choose if a password is needed to reset safeties. This password
can be either the user password either the service password.
When the user is logged in with a password, this password will be remembered. When the controller
is not touched for a specified time “LOGOUT TIMER” (user advanced menu), the controller will
automatically logout and password is needed again to enter the menu.
The user can find back in the password menu with which password he is logged on and he can also
manually log off.
Overview of
possibilities
A user password is used to protect the user parameters. This password can be set in the user
password menu.
A service password is used to protect the service parameters; this password is factory set and cannot
be changed.
User password Service password
1234 (default)
Contact your dis-
tributor for this
password (fixed)
1. Setpoint menu (only if Setpoint password is
enabled in the user advanced menu)
Yes Yes
2. User settings menu Yes Yes
3. Service menu No Yes
4. User password menu Yes Yes
Additionally: depending on the status of the "password needed to reset safety" parameter in the
service menu.
5. Possible to reset a safety in safety menu if
user password is required
Yes Yes
6. Possible to reset a safety in safety menu if
service password is required
No Yes
Possible to enter with
Menu