Daikin EWYQ230DAYN [322/524] Arec 005m

Daikin EWYQ230DAYN [322/524] Arec 005m
The Digital Controller For Multiscroll Chillers ESIE06-05
2–96 Part 2 – Functional Description
3
1
2
4
5
Compressor and
Unit Restart Timers
This screen allows modification of the compressor timers and unit restart timer.
Settings:
GRD : Guard timer setting
AREC : Anti recycling timer setting
RESTART POWER ON : When the unit is powered up after a power failure / main
switch, the unit can restart (automatic restart) after 30 sec.
REF GRD EXTEND Refrigerant guard extendtimer, when unit is switched off on
refrigerant gas temperature safety. The compressor can only
restart after 12 min (default).
_^ RESTART SAFETY
GRD:03m
RESTART POWERON:030s
REF GRD EXTEND:12m
AREC:005m