ESIE06-05 The Digital Controller For Multiscroll Chillers
Part 2 – Functional Description 2–87
3
2
4
5
1
D III
Communication
Parameters
This screen allows modification of the communication PCB parameters (DICN settings, ...).
Settings:
Remark: The DICN functionality can be used in combination with the D-BACS functionality.
This screen allows modification of the BMS control setting.
Settings:
D III: : YES: D III communication enabled
No : D III communication disabled
ADDR :
---: No address selected
“1-00” to “8-15”: address selected
POWER :
If a D-BACS device is present (iManager, ...) DIII power
parameter: “N” on all units
If no D-BACS device is present only for DICN DIII power
parameter: “Y” on only 1 unit (Master unit)
AIRNET : Airnet address (1-64)
AUTO :
YES: Chiller send information automatic to Airnet
NO: Airnet must request chiller data each time
_
DIII:YES
COMMUNICATION PCB
ADDR:---
AIRNET:01
POWER:Y
AUTO:Y
BMS CONTROL ALLOWED : If set to Y (yes), the unit can be commanded and
configured from a supervisory system.
If set to N (no), the supervisory system can only read out
values but cannot modify them.
_^
BMSCONTROL ALLOWED:N