Daikin EWYQ230DAYN [398/524] Low pressure bypass

Daikin EWYQ230DAYN [398/524] Low pressure bypass
Functional Control for a Standalone Unit ESIE06-05
2–172 Part 2 – Functional Description
3
1
2
4
5
3.24 Low pressure bypass
To avoid low pressure during startup of the unit or fan shifting (Fan up) the low pressure error is
disabled for a certain time.
The low pressure bypass can be set in the service safety menu.
FAN LP MASK : 30s (default)
Low pressure mask after switching to a higher fanstep.
COMPR LP MASK : 30 s (default)
Low pressure mask from first compressor start of a circuit (no masking at second compressor start).